TPI HLA Series 7.5KW Hazardous Location Fan Forced Unit Heater, 3P - 480 Volts
Model Number: HLA12-480360-7.5-24
Important Order Information: Please note: Orders for this item are non-cancellable once placed. Features: - Designed for rugged industrial applications in hazardous locations where the possibility of explosion or fire exists due to the presence of certain flammable gases, vapors, powdered metals or dust
- Permanently sealed, liquid to air, finned tube heat exchanger core
- Ethylene Glycol to water mixture used as a heat transfer fluid in the heater core, providing -45° C. (-49° F) freeze damage protection
- High-performance electric motor driven fan blows air across finned tubes to effect uniform heat transfer and area heat distribution
- Manual Reset capillary type limit provides high temperature regulation and is rated for 6,000 cycles of service
- Stainless steel and aluminum pressure relief valve for overpressure
- A back-up contactor is included for additional protection
- 14 gauge steel cabinet powder coated epoxy paint finish contains heater core, motor, and fan assembly
- Narrow gap safety fan guard shields all moving parts
- Adjustable louvers allow directional control of air
- Copper conductor wires enclosed in rigid metal conduits carry all electrical power
- Box lugs furnished for field connections within approved enclosure
- Made in U.S.A.
Specifications: - KW: 7.5
- BTUs: 25600
- Volts: 480
- PH: 3
- Amps: 9.7
- Control Voltage: 24
- Temp Rise °F: 41.4
- Air Throw: 24
- CFM: 580
- Recomd Mounting Ht.: 8
- WT.(LBS): 167
Note: Before selecting a hazardous location electric heater refer to Article 500 or other applicable standard referenced in the National Electric Code.